www.instrument.com - Saturday, March 13, 2010
Printer-friendly version of the page "EDAS-2005M Digital Output (FET) - 2 different models"
(URL: http://edasce.com/.html)
|
There are two FET digital output modules, both capable of switching DC signals, EDAS-2005M-1 and EDAS-2005M-2.
The EDAS-2005M-1 digital output module is capable of switching up to 24 VDC digital outputs.
The EDAS-2005M-2 high-voltage digital output module is capable of switching up to 360 VDC digital outputs.
Click here to request more information about the EDAS CE system
|
The EDAS-2005M-1 Digital Output Module provides 12 channels of open drain, 24 VDC digital outputs. The 12 channels are arranged as two ports. Port 0 has 8 channels and Port 1 has 4 channels. This module supports read back allowing the software to determine the output’s present state. Each channel has a hardware switch that determines the channels power-on state. An 8-position and a 4-position switch sets the initial data on these channels. When a switch is in the on position during the power-up reset, the corresponding channel will be turned on.
The digital outputs have 500 V channel to channel isolation with one return per channel. The module provides 1500 V input to output isolation.
Click here to request more information about the EDAS CE system
| Parameter | Conditions | Specifications | |
|---|---|---|---|
| Digital Output | 12 Outputs, 24VDC | ||
| On Resistance | .03 ohms typ. | ||
| On Current | 500mA | ||
| On Voltage | 0.8VDC max. | ||
| Off Voltage | 27VDC max. | ||
| Isolation | Channel - Channel | 500V | |
| Input to Output | 1500V | ||
| Current Consumption | 5VDC | 160 mA max | |
| Dimensions | Inches | 4.55D x 5.9H x 1.74W | |
| mm | 116D x 150H x 42W | ||
| Operating Temperature Range | 0 to 60° C* | ||
| *All specifications are typical at 25° C unless otherwise noted. Maximum voltage or current are dependent on power dissipation. Please contact support for particular current/voltage operating points. | |||
|
The EDAS-2005M-2 High Voltage Digital Output Module provides 12 channels of open drain, 360 VDC digital outputs. The 12 channels are arranged as two ports. Port 0 has 8 channels and Port 1 has 4 channels. This module supports read back allowing the software to determine the output’s present state. Each channel has a hardware switch that determines the channels power-on state. An 8-position and a 4-position switch sets the initial data on these channels. When a switch is in the on position during the power-up reset, the corresponding channel will be turned on.
The digital outputs have 500 V channel to channel isolation with one return per channel. The module provides 1500 V input to output isolation.
Click here to request more information about the EDAS CE system
| Parameter | Conditions | Specifications | |
|---|---|---|---|
| Digital Output | 12 Outputs, 360VDC | ||
| On Resistance | 5 ohms typ. | ||
| On Current | 260mA | ||
| On Voltage | 2VDC max. | ||
| Off Voltage | 360VDC max. | ||
| Isolation | Channel - Channel | 500V | |
| Input to Output | 1500V | ||
| Current Consumption | 5VDC | 160 mA max | |
| Dimensions | Inches | 4.55D x 5.9H x 1.74W | |
| mm | 116D x 150H x 42W | ||
| Operating Temperature Range | 0 to 60° C* | ||
| *All specifications are typical at 25° C unless otherwise noted. Maximum voltage or current are dependent on power dissipation. Please contact support for particular current/voltage operating points. | |||
Copyright 1996-2010 Intelligent Instrumentation Inc.